Elon Musk wrote on X on 31 October that there will be “a total of around 1.2M Blackwells at Colossus 2 by end of year”. If all of them sat in GB300 NVL72 racks at HPE’s published spec, they would draw about 2.2 GW of rack power, by our arithmetic, before cooling.
That is about 1.8 times the 1.2 GW of self-generating capacity that Mississippi permitted xAI in March, according to DatacenterDynamics. The post had about 1.19 million views by Sunday evening.
Business Pill · Lead Time Explained
A short explainer on lead times: why big infrastructure takes years from plan to operation. It teaches the general idea only and says nothing about this story.
The key insight: By our arithmetic on HPE’s published rack figures, the 1.2M Blackwells Musk posted would draw about 2.2 GW of rack power, about 1.8 times the 1.2 GW of on-site gas generation Mississippi permitted xAI.
What Musk Posted
Musk’s post, a reply to the account @XFreeze, reads: “There will be a total of around 1.2M Blackwells at Colossus 2 by end of year”. On 31 October he also named four Colossus 2 buildings holding about 860,000 GB300s between them, as we reported in Musk Says Colossus 2 Will Hold 1.2M Blackwells by Year-End.
On 1 November, Chamath Palihapitiya quoted the post and wrote: “Power is THE binding constraint in AI/SI. Few really have it.” We set his argument against company filings in Chamath Calls Power AI’s Limit; Filings Fold It Into Chips.

What Was Posted on X
Elon Musk posted on 31 October, replying to the account @XFreeze: “There will be a total of around 1.2M Blackwells at Colossus 2 by end of year”. The post had about 1.19 million views by 1 November.
Chamath Palihapitiya quoted Musk’s post on 1 November and wrote: “Power is THE binding constraint in AI/SI. Few really have it.” He added: “Solving power allows you to disproportionately shape AI/SI right now.”
The Rack Arithmetic
HPE’s QuickSpecs for its version of the rack, dated 8 September 2026, say the system holds “72 NVIDIA Blackwell Ultra GPUs” and that “The rack’s TDP (thermal design power) is 132 kW nominal with an EDPp (electrical design power โ peak) of approximately 155 kW”.
Dividing 1.2 million GPUs by 72 gives about 16,700 racks, by our arithmetic. At 132 kW each, that is about 2.2 GW. At the 155 kW peak it is about 2.58 GW.
HPE also writes that it “suggests that data centers should provision their bus ways to be able to support 192 kW EDPp”. Provisioned at that level, the same racks would need about 3.2 GW of electrical capacity, by our arithmetic.
What xAI Has Permitted
DatacenterDynamics reported on 11 March that “xAI has received permission to install 41 natural gas turbines at a site in Mississippi that will generate 1.2GW to power its data centers in the area”.
The report says the turbines, at a former Duke Energy plant site in Southaven, “will be used to power xAI’s Colossus 2 data center” and “will also supply power to the firm’s upcoming Colossus 3 data center in Mississippi”. xAI said on X it was “thrilled that MDEQ approved our permanent construction permit unlocking 1.2GW of self-generating power capacity”.
The court’s 30 October order listed at least 27 turbines on the Southaven site as of 7 April, with a combined capacity of 495 MW, as we calculated in the NAACP suit piece.
The Business Lever: GPUs and Permitted Power
As we read the figures together, the GPU count Musk posted implies a power need larger than the gas capacity xAI has permitted on site, and that permit is shared with a second data center.
The Structural Read
As we read HPE’s QuickSpecs, a GB300 NVL72 rack holds 72 Blackwell Ultra GPUs at 132 kW nominal, so 1.2 million GPUs means about 16,700 racks, by our arithmetic.
As we read DatacenterDynamics’ March report, the 1.2 GW permit covers 41 gas turbines in Southaven that serve Colossus 2 and the upcoming Colossus 3.
As we read the court’s 30 October order, as we calculated earlier, at least 27 turbines with 495 MW of capacity were on the site as of 7 April.
HPE, NVIDIA GB300 NVL72 by HPE QuickSpecs, 8 September 2026
“The rack’s TDP (thermal design power) is 132 kW nominal with an EDPp (electrical design power โ peak) of approximately 155 kW”
Three Implications
FOR XAI’S POWER PLANS By our arithmetic, the rack power for 1.2M GB300-class GPUs is about 2.2 GW against 1.2 GW of permitted on-site gas, a permit that also serves Colossus 3.
FOR DATA CENTER DESIGNERS HPE suggests provisioning bus ways for 192 kW per rack; at that level the same racks would need about 3.2 GW, by our arithmetic.
FOR THE POWER DEBATE Chamath Palihapitiya, quoting Musk’s post, wrote that power is THE binding constraint in AI; the figures above put numbers on that claim for one campus.
The Business Engineer Lens
This story maps onto the Business Engineer framework The State of AI Data Centers.
The framework says “Companies that solve the power equation will dominate the AI era; those that don’t will watch their chips sit idle.”
As we read it, Musk’s GPU count and xAI’s permitted gas capacity are the two sides of that power equation for one campus. The framework predates Musk’s post and does not discuss Colossus 2.
Related coverage: Musk says Colossus 2 will hold 1.2M Blackwells · Chamath calls power AI’s limit · Judge lets NAACP suit over xAI’s turbines proceed · This Week in the AI Supercycle
What Is Not Established
Musk’s post gives a GPU count, not a power figure, and xAI has not published Colossus 2’s total power draw in what we read. Our 2.2 GW assumes every GPU sits in a GB300 NVL72 rack at HPE’s published figures; Colossus 2 also runs GB200s, as Musk wrote in September, and their racks differ. The figures are rack power only, before cooling and other facility overhead. We did not size xAI’s grid supply, so the 1.8 times comparison covers only the permitted on-site gas capacity.
The Bottom Line
Musk wrote that Colossus 2 will hold around 1.2 million Blackwells by year-end. At HPE’s published GB300 NVL72 spec, that is about 16,700 racks and about 2.2 GW of rack power by our arithmetic, roughly 1.8 times the 1.2 GW of on-site gas generation Mississippi permitted xAI in March.
95,000+ executives read Business Engineer for the AI strategy frameworks cited by ChatGPT, Claude, and Perplexity.
A note on sourcing. The GPU count is Elon Musk’s own post; the power figures are our arithmetic on HPE’s published GB300 NVL72 rack specification and assume every GPU sits in such a rack; the 1.2 GW permit is as reported by DatacenterDynamics. Neither Musk nor xAI has published Colossus 2’s total power draw in what we read.
Sources: Elon Musk on X, 31 October 2026 · HPE, NVIDIA GB300 NVL72 by HPE QuickSpecs, Version 3, 8 September 2026 · DatacenterDynamics, Musk’s xAI gets go-ahead for 41 natural gas turbines in Mississippi, 11 March 2026 · Chamath Palihapitiya on X, 1 November 2026